LoRaWAN Payload Description - Raumsensor Device

Port: 2 Length: 7 bytes Format: Binary

Byte Field Type Unit Description
0-1 Room Temperature int16_t 0.01°C SHT4x sensor reading (big-endian)
2-3 Floor Temperature int16_t 0.01°C MLX90614 IR sensor reading (big-endian) *
4-5 Humidity int16_t 0.01% SHT4x sensor reading (big-endian)
6 Relay State uint8_t - Current relay status (0=OFF, 1=ON)

Example Uplink:

  • 08 34 0A 28 15 E0 01 = 21.00°C room, 26.00°C floor, 56.00% humidity, relay ON

Port: Any Format: Binary

Combined Configuration Packet

Length: 3 bytes Format: [heating_enable][room_temp_threshold][floor_temp_threshold]

Byte Field Type Range Description
0 Heating Enable uint8_t 0-1 Heating control logic (0=DISABLED, 1=ENABLED)
1 Room Temperature Threshold uint8_t 0-255 Target room temperature in °C
2 Floor Temperature Threshold uint8_t 0-255 Target floor temperature in °C

Examples:

  • 01 16 19 = Enable heating, room 22°C, floor 25°C
  • 00 14 18 = Disable heating, room 20°C, floor 24°C

Send Interval Command

Length: 2 bytes Format: 'i'[interval_minutes]

Byte Field Type Range Description
0 Command ASCII 'i' (0x69) Send interval command identifier
1 Interval uint8_t 1-255 Send interval in minutes

Examples:

  • 69 05 = Set send interval to 5 minutes
  • 69 3C = Set send interval to 60 minutes

Data Conversion

  • Temperature: value = (int16_t)(temperature * 100)
  • Humidity: value = (int16_t)(humidity * 100)
  • Decoding: actual_value = received_value / 100.0

Special Cases

* Floor Temperature Sensor: If the MLX90614 sensor is not available or not responding, the floor temperature will be transmitted as -273.15°C (hex: 95 5D).